Picture Window - Performance Report


Product Identification
Product Type: Fixed Window
Series/Model #: 500 Replacement (Model: 500-PW-T001) Fixed Window
Specification: AAMA/NWWDA 101/I.S.2-97
Designation: F-R35 (60" X 60") AAMA/NWWDA 101/I.S.2-97 GRADE 35

General:
Test sample was comprised of 500 Replacement, Picture Vinyl Window, with an overall master frame size measuring 60" wide X 60" high X 3-1/4" depth. The frame was of welded mitered type corner construction.

Weather-Stripping:
None

Operators and Other Hardware:
None

Glazing System:
The fixed lite was interior drop glazed with 3/4" (nominal) thick insulated glass. The fixed lite utilized two (1/8" nominal) thick clear annealed glass lites with a 1/2" perimeter metal spacer. The glazing was set on a bead of silicone along the perimeter of the frame. A interior snap-in rigid vinyl-glazing bead secured the glass.

Weep Holes:
Two (5/16" diameter) weep holes were located on the bottom of the glazing track, one 2-3/4" from each end. Two (1-3/8" w x 5/16"h reduced to 1-3/16" w x 1/8" h) weep slots with flap were located on the exterior face of the sill, one 2-3/4" in from each end. Two (9/16" w x 9/16" ht x 25/32" diagonal) triangular weeps at each end of sill on innermost interior wall of the sill.

Sealant:
Silicone sealant was applied to all the following areas:
* Perimeter of the glazing was set in continuous bead of silicone.
* Exterior face of frame to buck intersection.

Anchorage:
Silicone sealant was used around the exterior perimeter of the frame to buck intersections. Two (#8 x 2" long ) screws were used for each jamb to secure the frame to the buck, one 5-3/4" from each end.
 

500 PICTURE FIXED WINDOW (REPLACEMENT)
(MODEL 500-PW-T001)
Test Results:

Test Title / Referenced Test Method Test Results Allowable
Gateway Performance Requirements    
Air Infiltration Test (ASTM E-283-91)
@ 1.57 psf
The test specimen meets the performance levels specified in
AAMA/NWWDA 101/I.S.2-97 for Air Infiltration.
0.02 cfm/sf 0.30 cfm/sf
Water Resistance Test (ASTM E547-96)
@ 2.86 psf (w/wo screen)
No Penetration No Penetration
Uniform Load Structural Test
(see optional performance results)
   
Welded Corner Test Meets As Stated
Forced Entry Resistance (ASTM F588-97) Type D (Section 10)    
Sec. 10.2.4.2 Hand & Tool
Manipulation Test
No Failure As Stated
Specific Window Performance Results    
Optional Performance Results    
Water Resistance Test (ASTM E547-96)
@ 8.25 psf
No Penetration No Penetration
Uniform Load Structural Test (ASTM E-330-96)   (0.4%xL)
@ 52.5 psf positive 0.002" * 0.192"
@ 52.5 psf negative 0.079" * 0.192"

* - Maximum Deformations.
 

 